Home / Services / Water Heater Venting Repair

Water Heaters · Venting

Water Heater Venting Repair

Water heater venting repair fixes a gas tank whose exhaust spills back into the house at the draft hood instead of rising up the vent, a fault called backdrafting. If a carbon monoxide alarm has sounded, leave the house and call from outside. If you see scorch marks, melted plastic or moisture on top of the tank, turn the control to its vacation or pilot setting and book a visit; the repair is one of three things: correct the vent connector, line the chimney, or change to a power-vent or direct-vent tank.

Reviewed by Zobir, licensed technician

A standard gas tank has no fan. Hot exhaust rises through the centre flue, mixes with room air at the draft hood on top and floats up the vent because it is lighter than the air around it. Anything that cools that column, blocks it or pulls against it sends the exhaust out around the hood instead. The evidence collects on top of the tank: melted plastic rings where the water pipes enter, brown scorch marks around the hood, rust, and beads of moisture.

The most common cause in Halton and Hamilton is a furnace upgrade. In the 1970s–90s subdivisions the furnace and water heater shared one chimney; when the furnace is replaced with a condensing unit vented in plastic through the wall, the water heater is left alone on a flue sized for both. Its small burner cannot warm that much chimney, so the exhaust stalls and condenses. In pre-war brick houses with unlined masonry chimneys, that condensate also eats the mortar and drops debris into the flue.

The other causes are simpler. A vent connector that runs flat or slopes back toward the tank, has too many elbows, or was sized wrong; a chimney cap blocked by a nest or ice; and house depressurisation, where a range hood, clothes dryer and bath fans in a tightened-up house pull air down the flue because it is the easiest way in. The test is done under the worst case: fans and dryer running, doors closed, burner firing for five minutes, then a smoke test at the hood and a carbon monoxide reading in the room. How to tell if a water heater is backdrafting shows the homeowner version.

The fix follows the cause. A connector is re-pitched so it climbs steadily to the chimney, shortened, or resized to the appliance. An oversized or unlined chimney gets a liner sized to the water heater. And where the chimney is not worth saving, or the house keeps going negative, the tank is replaced with a power-vent or direct-vent model that no longer depends on the chimney: a new tank runs $1,200–$2,500 installed depending on size and venting.

Signs a water heater is backdrafting

  • Melted or deformed plastic rings where the water pipes enter the top of the tank
  • Brown or black scorch marks around the draft hood, or soot on the tank top
  • Rust on the top of the tank and the vent connector, or water dripping from the hood
  • Warm, damp air or a hot exhaust smell near the tank while the burner runs
  • A carbon monoxide alarm sounding: get everyone out first, then call 911 from outside

How it works

1. Make it safe

On the phone we tell you whether to shut the tank down now. On site the first readings are carbon monoxide in the room and at the draft hood.

2. Worst-case draft test

Exhaust fans and the dryer are switched on, interior doors are closed and the burner is fired. The technician checks spillage at the hood, the slope and size of the connector, and the chimney from the base, and from the roof where the cap is suspect.

3. Fix and prove it

The connector, liner or tank replacement is carried out by a TSSA-licensed technician, and the same worst-case test is repeated to show the exhaust now leaves the house. The readings go on your invoice; book a venting inspection.

Common questions

Is it safe to keep using the water heater until the visit?

Not if a carbon monoxide alarm has sounded or you can see scorching and melted plastic; turn the gas control to vacation or off and use the visit to find out why. If the only sign is some rust or occasional moisture, confirm you have a working CO alarm outside the bedrooms, which Ontario requires in homes with fuel-burning appliances, and book a test this week.

Why did this start after the new furnace went in?

Because the old furnace was doing most of the work of heating the chimney. With it gone, the water heater is venting alone into a flue that is too large and too cold for it. This should be checked whenever a furnace comes off a shared chimney, and a liner sized for the remaining appliance is the usual correction.

Does it backdraft only in certain weather?

It can. Draft is weakest on mild, damp days when the chimney is barely warmer than the outdoors, and strong wind can push down a short chimney. The more common trigger is inside the house: the dryer, the range hood and bath fans running together. A tank that spills only under those conditions still needs fixing, because that is an ordinary evening.

Will a power-vent tank solve it for good?

It takes the chimney out of the picture. A fan pushes the exhaust out through plastic pipe in the side wall, so chimney size, liners and caps no longer matter. A direct-vent tank goes further and takes its combustion air from outside, which suits tightly sealed houses. The trade-offs, including the power supply a fan needs, are in power vent vs conventional vent water heaters.

The tank is a rental. Is the venting my problem?

The appliance is the rental company's; the chimney is part of your house. If the fault is the tank's draft hood or connector, call the rental company first. If it is the chimney or house depressurisation, expect them to point back to you. We can test and tell you which it is in writing, and our water heater service covers replacing a rental with an owned tank.